image image image image image image

Shop

6 kV SVL

Sheath voltage limiters reduce risk of cable damage by limiting transient voltages on cable sheaths

Datasheet of 6 kV SVL
Model PPSAC2-06
Arrester Housing Polymeric
Application Indoor
Applicable Standard IEC 60099-4 / IS 3070 Part 3
Rated Voltage of the Arrester (Ur) 6 kV
Maximum Continuous Operating Voltage (MCOV) 5.1 kV
Nominal Discharge Current (NDC) 10 kA
Line Discharge Class 2
High Current Impulse 100 kA
Energy Capability 4 kJ /kV at Ur according to IEC 60099-4
Internal Partial Discharge (≤) 10 pC
1 Minute Power Frequency Voltage 30 kV
Standard Lightning Impulse Voltage (1.2/50 µsec.) 75 kV
Creepage Distance 130 mm
Height 148 mm
Test Carries Out
  • Power frequency voltage Test
  • Lightning Impulse voltage Test
  • Internal Partial discharge Test